A Flammable Liquid is a combustible liquid which can be easily ignited in air at ambient temperatures. (e.g., acetone, biodiesel, diesel, ethanol, and gasoline, etc.) Flammable Liquid is any liquid that has a closed-cup flash point below 100 °F (37.8 °C), as determined by the test procedures described in NFPA 30 and a Reid vapor pressure not exceeding 40 psia (2068.6 mm Hg) at 100 °F (37.8 °C), as determined by ASTM D 323, Standard Method of Test for Vapor Pressure of Petroleum Products (Reid Method). Class IA liquids shall include those liquids that have flash points below 73 °F (22.8 °C) and boiling points below 100 °F (37.8 °C). Class IB liquids shall include those liquids that have flash points below 73 °F (22.8 °C) and boiling points at or above 100 °F (37.8 °C). Class IC liquids shall include those liquids that have flash points at or above 73 °F (22.8 °C), but below 100 °F (37.8 °C).